Hearth and Home Technologies Grand-XT Outdoor Fireplace User Manual


 
18
Installing the Insert (continued)
Figure 3. Minimum height from roof to lowest
discharge opening
ROOF PITCH H (MIN.) FT.
Flat to 6/12 1.0
6/12 to 7/12 1.25
Over 7/12 to 8/12 1.5
Over 8/12 to 9/12 2.0
Over 9/12 to 10/12 2.5
Over 10/12 to 11/12 3.25
Over 11/12 to 12/12 4.0
Over 12/12 to 14/12 5.0
Over 14/12 to 16/12 6.0
Over 16/12 to 18/12 7.0
Over 18/12 to 20/12 7.5
Over 20/12 to 21/12 8.0
!
WARNING: MAJOR U.S. BUILDING CODES
SPECIFY MINIMUM CHIMNEY AND/OR VENT
HEIGHT ABOVE THE ROOF TOP. THESE
MINIMUM HEIGHTS ARE NECESSARY IN THE
INTEREST OF SAFETY. SEE THE FOLLOWING
DIAGRAM FOR MINIMUM HEIGHTS, PROVIDED
THE TERMINATION CAP IS AT LEAST 2-FEET
FROM A VERTICAL WALL AND 2 FEET BELOW
A HORIZONTAL OVERHANG.
Note: This also pertains to vertical vent systems installed
on the outside of the building.
PENTE DU TOIT H (MINI.) EN CM
De plat à 6/12 30
De 6/12 à 7/12 38
De 7/12 à 8/12 46
De 8/12 à 9/12 61
De 9/12 à 10/12 76
De 10/12 à 11/12 99
De 11/12 à 12/12 122
De 12/12 à 14/12 152
De 14/12 à 16/12 183
De 16/12 à 18/12 213
De 18/12 à 20/12 229
De 20/12 à 21/12 244
Installation de la cassette (suite)
!
AVERTISSEMENT : LES PRINCIPAUX CODES DE
CONSTRUCTION AMÉRICAINS DÉFINISSENT LA
HAUTEUR MINIMALE DE LA CHEMINÉE ET/OU
DU CONDUIT D’ÉVACUATION AU-DESSUS DU
TOIT. CES HAUTEURS MINIMALES SONT
NÉCESSAIRES POUR DES RAISONS DE
SÉCURITÉ. CONSULTEZ LE SCHÉMA SUIVANT
POUR CONNAÎTRE LES HAUTEURS MINIMALES
À RESPECTER LORSQUE LE CAPUCHON EST
ÉLOIGNÉ D’AU MOINS 61 CM D’UN MUR
VERTICAL ET AU-DESSOUS D’UN SURPLOMB.
Remarque : Ces restrictions s’appliquent également aux
systèmes d’évacuation verticale installés à l’extérieur de
l’édifice.
Figure 3. Hauteur minimum entre le toit et
l’ouverture d’évacuation la plus
basse
HORIZONTAL OVERHANG
(SURPLOMB)
VERTICAL WALL
(MUR VERTICAL)
TERMINATION CAP
(CAPUCHON)
12
X
ROOF PITCH IS X/ 12
(LA PENTE DU TOIT EST DE X/12)
LOWEST
DISCHARGE
OPENING
(L’OUVERTURE
D’ÉVACUATION LA
PLUS BASSE)
H (MINI.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
(H (MINI) - HAUTEUR MINIMUM ENTRE LE TOIT
ET L’OUVERTURE D’ÉVACUATION LA PLUS BASSE)
2 FT
(61cm)
MINI.
2 FT (61cm)
MINI.