Desa EVDDVF36PN Fire Pit User Manual


 
10
106573
DIRECT-VENT GAS FIREPLACE
EVDDVF36PN and EVDDVF36STN
®
VENTING
INSTALLATION
Continued
UP
Figure 21 - Horizontal Termination Configuration for Rigid Venting Using One
90° Elbow
Figure 22 - Horizontal Termination Using Flexible Venting
Horizontal Venting
Vertical (V) Horizontal (H)
49.5" min. 15" max.
(45° elbow, 1' vertical pipe, 90° elbow)
61.5" min. 34" max.
73.5" min. 58" max.
85.5" min. 10' max.
102.5" min. 20' max.
UP
Horizontal Venting
See information in
Figure 21 for
Vertical(V) and
Horizontal(H) maxi-
mums and minimums.
The same amounts
apply for flexible
venting.
FGFVK Vent Kit Shown
Horizontal Termination
Configurations
Figures 21 through 23 show different con-
figurations for venting with horizontal ter-
mination. Each figure includes a chart with
vertical minimum/maximum and horizon-
tal maximum dimensions which must be
met. All connections must be sealed with
high temperature silicone sealant as speci-
fied in the second warning statement on
page 7. All horizontal terminations require
1/4" rise per 12" of horizontal run.
Note:
The 30° Starter
Elbow Must Be
Discarded and
Replaced with a 45°
Starter Elbow.
45° Starter
Elbow
Required