Hearth and Home Technologies CARDOG42I Outdoor Fireplace User Manual


 
Outdoor Lifestyles by Hearth & Home Technologies Inc. • Carolina • 4066-300 • Rev. Q • 7/11 9
Fireplace Structure
Noncombustible mat’l
Mantel
25 in.
(635 mm)
minimum
6 in.
(151 mm)
minimum - one side only.
Alcove installations require
14 in. (356 mm) from each side
of the firebox opening.
82 in.
(2083 mm)
minimum
height
Additional Structure
or Sidewall
Ceiling or
Overhang
12 in. (305 mm)
max. combustible
mantel depth
49-1/2 in.
(1257 mm)
minimum
16 in.
(406 mm)
deep non-combustible
hearth extension recommended
when floor in front is combustible.
Figure 3.3 Clearances
WARNING! Risk of Fire!
Comply with all minimum
clearances to combustibles as
speci ed. Framing or nish-
ing material closer than the
minimums listed must be con-
structed entirely of non-com-
bustible materials (i.e., steel
studs, concrete board, etc).