Hearth and Home Technologies CARDOG42I Outdoor Fireplace User Manual


 
Outdoor Lifestyles by Hearth & Home Technologies Inc. • Carolina • 4066-300 • Rev. Q • 7/11 6
A. Select Appliance Location
Refer to Figures 3.1, 3.2 and 3.3.
When selecting a location for your appliance it is important
to consider where the appliance is to be installed:
- Clearance to side walls
- Location of adjacent stairwells
- Doors
- Windows
- Walkways
- Wires
- Possibility of ooding or running water
3
3
Framing and Clearances
WARNING! Risk of Fire or Burns! The appliance is hot and
wind may cause ames to reach out in front.
Keep furniture, draperies and other combustibles away.
Locate the appliance away from traf c areas.
Do not block air openings.
DO NOT place rugs, carpeting or other combustible
materials on the oor directly in front of the appliance.
Clean up fallen leaves, branches and other combustible
materials before using the appliance.
See Figure 3.1 for required clearances.
CAUTION! The appliance is hot and wind may cause
ames to reach out in front. Install on wood or solid
noncombustible surfaces extending full width and depth to
prevent damage.
DO NOT install directly on carpeting, vinyl, plastic com-
posite decking or combustible surfaces other than wood.
When installed on wood, a 16” noncombustible hearth
extension in front of the appliance is recommended.
See Figure 3.3.
NOTICE:
Illustrations re ect typical installations and are for
DESIGN PURPOSES ONLY. Illustrations/diagrams are not
drawn to scale. Actual installation may vary due to individual
design preference.
B. Stand-Alone Installation
This replace may be installed as a stand-alone unit.
Tape and seal all joints and corners.
• Provide proper ashing and moisture management if
installed on surfaces that may rot or otherwise be damaged
by water. (See also sections 3.C. and 3.D.)
When the stand-alone surround is constructed completely
of noncombustible materials, stand-offs may be removed to
permit a smaller structure.
Air space clearances are not required for stand-alone
construction with noncombustible materials.
C. Built-in Installation
When this replace is installed into a wall, we recommend
that the wall be an exterior wall system.
See framing measurements in Figure 3.1.
You must maintain 1 1/2 in. (38 mm) airspace at the sides
and back of the replace.
Header must be placed a minimum of 6 in. (152 mm) above
the top of the replace.
Noncombustible wall sheathing material is required the
rst 36 in. above the top of the rebox opening.
- Remove the existing top front (cement board) and
replace with 36 x 45 1/2 in. (minimum) cement board.
Allow overlap on the framing studs. See Figure 3.1.
The control box MUST be relocated to be easily accessible.
See Section 5.D.
Flash the perimeter of the replace, corners and the
fireplace face in a manner consistent with regional
practices as required to prevent water penetration around
the replace or manage water that may penetrate the
replace. See Section 3.D. and Figure 3.1 (CARODG36)
and 3.2 (CARODG42) for more information regarding wall
and enclosure construction.
D. Moisture Resistance
This outdoor replace will shed moderate amounts of wa-
ter, but is not waterproof. This appliance must be enclosed
or covered with noncombustible nish material and all joints
sealed to prevent water in ltration.
The replace re box will not perform as an exterior wall.
Moisture penetration must be considered for construction
that places the replace in structure walls or on moisture
sensitive surfaces.
When installed on exterior walls: Hearth & Home Tech-
nologies recommends that the replace chase be con-
structed outside the structure’s weather envelope. Where
the platform meets the wall, use a ashing detail similar to
that required for attached decks. Chase platforms, includ-
ing hearths should slope away from the structure at 1/8 in.
to 1/4 in. per foot. The replace can be shimmed level.
WARNING! Risk of Fire! Maintain speci ed air space
clearances to appliance:
Insulation and other materials must be secured to prevent
accidental contact.
The chase/enclosure must be properly blocked to prevent
blown insulation or other combustibles from entering and
making contact with replace or chimney.
Failure to maintain airspace may cause overheating and
a re.
NOTICE: Soot may accumulate on the area above the rebox
opening and may require periodic cleaning.