Desa (V)KC36PE Outdoor Fireplace User Manual


 
www.desatech.com
116238-01D 13

Recommended Applications:
Corner ground oor installation
Ground oor installation where pipe vents horizon-
tally through wall (over 12" horizontal pipe)
Basement installation where one foot clearance
from ground to termination is possible
VENTING INSTALLATION INSTRUCTIONS
Continued
Figure 15 - Horizontal Termination Conguration for Corner Installation Using One
90° Elbow
Square
Termination
Wall
Firestop
Not to Exceed (H) Limits
As Required
for (V), See
Chart for
Pipe Section
Required
45° Elbow
90° Elbow
90° Elbow
Square
Termination
Wall
Firestop
45° Elbow
12" Min.

  
*43
1
/
2
" min. None 30" max.
54
1
/
2
" min. 1 ft. 48" max.
66
1
/
2
" min. 2 ft. 60" max.
78
1
/
2
" min. 3 ft. 84" max.
90
1
/
2
" min. 4 ft. 20' max.
* Ground Floor Corner Venting
Not to Exceed
(H) Limits

Recommended Applications:
Installations requiring a vertical rise on building exterior
Any installation using snorkel termination to achieve one foot above ground
Snorkel terminations are available for installations requiring a vertical rise on the exterior of the build-
ing. If installing snorkel termination below grade, you must provide proper drainage to prevent water
from entering snorkel termination (see Figure 16).
Do not back ll around snorkel termination.
Snorkel Termination
12"
Min.
Snorkel
Termination
Wall
Firestop
90° Elbow
45° Elbow
Figure 16 - Snorkel Termination Congurations for Below Ground Installation
Snorkel Termination
Adequate
Drainage
12" Min.
12" Min.