Installation / Assembly
As a safety precaution, remember to always leak test
your grill outdoors in a well-ventilated area. Never
smoke or permit sources of ignition in the area while
doing a leak test. Do not use a ame, such as a lighted
match to test for leaks. Use a solution of soapy water.
Prepare a leak testing solution of soapy water by 1.
mixing in a spray bottle one part liquid soap to one
part water.
Make sure all the control knobs are in the OFF po-2.
sition.
Turn on the gas. Turn the gas supply valve counter 3.
clockwise one turn to open.
Apply the leak-testing solution by spraying it on 4.
joints of the gas delivery system. Blowing bubbles
in the soap solution indicates that a leak is pres-
ent.
Stop a leak by tightening the loose joint or by re-5.
placing the faulty part with a replacement part rec-
ommended by the manufacturer.
Turn all control knobs back to the full OFF posi-6.
tion.
If you are unable to stop a leak:
Turn all control knobs back to the full OFF posi-1.
tion.
Shut off the gas supply to the grill and release 2.
pressure in the hose and manifold by pushing in
and turning any of the control valves one quarter
turn counter-clockwise.
Call an authorized gas appliance service techni-3.
cian.
Do not use the appliance until the leak is corrected.
Liquid Propane Gas
Tank Requirements
For plumbed-in LP installation, use a convertible regu-
lator and set it for LP gas.
Maximum line pressure for plumbed-in propane is 14”
WC (3.5 kPa). Minimum line pressure for propane is
11” WC.
Model Number Description Width Depth Height Cut-out for drop in accessories
BBQ08852U Drop In Standard Side
Burner
29.2 cm 45.1 cm 7.0 cm
WIDTH
DEPTH
HEIGHT
BBQ08953U Standard Side by Side
Burner
61.6 cm 50.2 cm 10.8 cm
BBQ08954U Deluxe Side by Side
Burner
64.1 cm 33.7cm 18.4 cm
Leak Testing Procedure
Perform a leak test at least once a year whether the gas supply has been disconnected or not. In addition, whenever
the gas supply is connected to the regulator or whenever any part of the gas system is disconnected or replaced,
perform a leak test.