Desa LCF24 Outdoor Fireplace User Manual


 
www.desatech.com
115043-01C
6
The fireplace must include a working flue and
venting system with the minimum openings shown
in the Figure 2.
INSTALLATION
Continued
Figure 2 - Technical Information Charts
Model
Burner
Descrip-
tion
BTU Input
(Natural
Gas)
Min.
Vent
Opening
LCF18 18" Dual 55,000 8"
LCF24 24" Dual 60,000 8"
Minimum Fireplace Dimensions
Model
Front
Width
Back
Width*
Depth Height
LCF18 28" 18" 14" 16"
LCF24 29.75" 17" 15.5" 18"
* At depth Indicated
Fuel Inlet Pressure
Specifications (W.C.)
Min. Max.
N.G. 5.5" 10.5"
Burner Orifice Sizing
Log Size
Natural Gas
In. Num.
18" .120 31
24" .129 30
CHECK GAS TYPE
Use only natural gas. If your gas supply is not
natural gas, you must install ON/OFF Safety
Valve/Pilot Kit (see Accessories, page 18). Call
dealer where you bought log set.
If the fireplace does not have a gas supply shutoff
valve, one must be installed.
VENTING SPECIFICATIONS FOR
INSTALLATION
The fireplace chimney flue and vent must be draft-
ing properly. To check the vent for proper drafting:
Light a tightly rolled newspaper on one end and
place it at the inside front edge of the fireplace.
Observe the smoke and be sure the vent is properly
drawing it up the chimney. If the smoke spills out
into the room, extinguish the flame and remove any
obstruction until proper venting is achieved.
The chimney flue must remain open a minimum
of 3" at all times during the operation of this
log set.
INSTALLING DAMPER CLAMP
Secure the damper stop clamp provided to the
leading edge of the damper as shown in Figure 3.
If for any reason this clamp doesn't work on your
fireplace, another suitable clamp or permanent
stop must be installed, or the damper blade must
be cut or removed.
CONNECTING TO GAS SUPPLY
WARNING: A qualified ser-
vice person must connect log
set to gas supply. Follow all
local codes.
Installation Items Needed
Before installing log set, make sure you have the
items listed below.
piping (check local codes)
sealant (resistant to Propane/LP gas)
equipment shutoff valve
test gauge connection
adjustable (crescent) wrench or pliers
sediment trap
tee joint
pipe wrench
Figure 3 - Attaching Damper Clamp
Damper
Clamp
Damper
Clamp
Damper
Manufactured
Fireplace
Masonry Fireplace
Damper