Step 12
Install gas supply
General Specifications for Piping
Note - Contact your local municipality for building
codes regulating outdoor gas barbecue
installations. In absence of Local Codes, you must
conform to the latest edition of ANSI Z223.1. WE
RECOMMEND THAT THIS INSTALLATION BE DONE
BY A PROFESSIONAL.
Some of the following are general requirements taken
from ANSI Z223.1, for gas supply installations. Refer to
ANSI Z223.1 latest edition for complete specifications.
Note: The LP gas supply at the barbecue must be
regulated to 10.5 inches of water column pressure.
A manual shut-off valve must be installed outdoors,
immediately ahead of the quick disconnect.
ƽCAUTION: If young children are in the area, a
locking valve should be considered.
An additional manual shut-off valve indoors should
be installed in the branch fuel line in an accessible
location near the supply line.
The quick disconnect connects to a 3/8 inch NPT
thread from the gas source. The quick disconnect
fitting is a hand-operated device that automatically
shuts OFF the flow of gas from the source when the
barbecue is disconnected.
The quick disconnect fitting can be installed
horizontally, or pointing downward. Installing the
fitting with the open end pointing upward can result
in collecting water and debris.
The dust covers (supplied plastic plugs) help keep
the open ends of the quick disconnect fitting clean
while disconnected.
Pipe compound should be used which is resistant to
the action of propane gas when connections are
made.
The outdoor connector must be firmly attached to
rigid, permanent construction.
Typical propane gas supply installation. Figure 14.
Gas line piping
If the length of line required does not exceed 50
feet, use a 5/8" O.D. tube. One size larger should be
used for lengths greater than 50 feet.
Gas piping may be copper tubing, type K or L;
polyethylene plastic tube, with a minimum wall
thickeness of .062 inch; or standard weight
(schedule 40) steel or wrought iron pipe.
Copper tubing must be tin-lined if the gas contains
more than 0.3 grams of hydrogen sulfide per 100
cubic feet of gas.
Plastic tubing is suitable only for outdoor,
underground use.
Gas piping in contact with earth, or any other
material which may corrode the piping, must be
protected against corrosion in an approved manner.
Underground piping must have a minimum of
18" cover.
Test connections
All connections and joints must be thoroughly tested for
leaks in accordance with local codes and all listed
procedures in the latest edition of ANSI Z223.1.
Gas supply
Shut off
Locking shut off
Inside wall
Outside wall
Quick Disconnect
Figure 14
The quick disconnect is installed
above ground
ƽ DANGER ƽ
Do not use an open flame to check for
gas leaks. Be sure there are no sparks or
open flames in the area while you check for
gas leaks. This will result in a fire or
explosion which can cause serious bodily
injury or death, and damage to property.