WARNING: For propane/LP
units, make sure external regula
-
tor has been installed between
propane/LP supply and heater.
See guidelines under
Installing
Gas Piping to Fireplace Loca-
tion, page 13.
PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect appliance with its appliance main
gas valve (control valve) and equipment
shutoff valve from gas supply piping system.
Pressures in excess of 1/2 psig will damage
fireplace gas regulator.
2. Cap off open end of gas pipe where equipment
shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve for
propane/LP gas or opening main gas valve
located on or near gas meter for natural gas,
or using compressed air.
4. Check all joints of gas supply piping system.
Apply noncorrosive leak detection fluid to all
joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Reconnect fireplace and equipment shutoff
valve to gas supply. Check reconnected fittings
for leaks.
Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Figure 17).
2. Pressurize supply piping system by either
opening propane/LP supply tank valve for
propane/LP gas or opening main gas valve
located on or near gas meter for natural gas,
or using compressed air.
3. Check all joints from gas meter for natural gas
or propane/LP supply to equipment shutoff
valve for propane/LP gas (see Figures 18 or
19). Apply noncorrosive leak detection fluid
to all joints. Bubbles forming show a leak.
4. Correct all leaks at once.
INSTALLATION
Continued
Figure 18 - Checking Gas Joints for
Natural Gas Fireplace
Figure 19 - Checking Gas Joints for
Propane/LP Gas Fireplace
Figure 17 - Equipment Shutoff Valve
Open
Closed
Equipment
Shutoff
Valve
Equipment
Shutoff Valve
Manual Gas Valve
Gas Meter
Equipment
Shutoff Valve
Manual Gas Valve
Propane/LP
Supply Tank
PRESSURE TESTING FIREPLACE GAS
CONNECTIONS
1. Open equipment shutoff valve (see Figure 17).
2. Open main gas valve located on or near gas
meter for natural gas or open propane/LP
supply tank valve.
3. Place manual ignition switch in the OFF
position.
4. Check all joints from equipment shutoff valve
to gas valve (see Figure 18 or 19). Apply
noncorrosive leak detection fluid to all joints.
Bubbles forming show a leak.
5. Correct all leaks at once.
6. Light fireplace (see Operating Fireplace, page
21). Check all other internal joints for leaks.
7. Turn off fireplace (see To Turn Off Gas to
Appliance, page 22).