Desa (V)K36N Outdoor Fireplace User Manual


 
www.desatech.com
111923-01D 17
FIREPLACE INSTALLATION
Continued
Installation must include an equipment shutoff valve, union, and
plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge
hook up. NPT tap must be upstream from replace (see Figure 31).
IMPORTANT: Install main gas valve (equipment shutoff valve)
in an accessible location. The main gas valve is for turning on or
shutting off the gas to the appliance.
Check your building codes for any special requirements for locating
equipment shutoff valve to replaces.
Apply pipe joint sealant lightly to male NPT threads. This will
prevent excess sealant from going into pipe. Excess sealant in pipe
could result in clogged replace valves.
WARNING: Use pipe joint sealant that is resistant
to liquid petroleum (LP) gas.
We recommend that you install a sediment trap/drip leg in supply
line as shown in Figure 31. Locate sediment trap/drip leg where it
is within reach for cleaning. Install in piping system between fuel
supply and replace. Locate sediment trap/drip leg where trapped
matter is not likely to freeze. A sediment trap traps moisture and
contaminants. This keeps them from going into replace gas con-
trols. If sediment trap/drip leg is not installed or is installed wrong,
replace may not run properly.
Figure 31 - Gas Connection
CSA Design-Certied
Equipment Shutoff Valve
with 1/8" NPT Tap*
3" Minimum
Approved Flexible
Gas Line
Cap Pipe Nipple Tee Joint
Sediment Trap/Drip Leg
Natural - From
Gas Meter (5.5"
W.C. to 10.5"
W.C. Pressure)
Propane/LP
From External
Regulator (11"
W.C. to 14" W.C.
Pressure)
* The CSA design-certied equipment shutoff valve may be supplied
with the appliance or you can purchase it from your retailer.

Installation Items Needed
5/16" hex socket wrench or nut-driver
sealant (resistant to propane/LP gas, not provided)
1. Open lower louver door panel by gently pulling forward.
2. Route exible gas line (provided by installer) from equipment
shutoff valve to replace. Route exible gas supply line through
one of the access holes on side of replace.
3. Attach exible gas line from gas supply to control valve (see
Figure 32).
4. Check all gas connections for leaks. See Checking Gas
Connections.
Figure 32 - Connecting Flexible Gas Line to Control Valve
Control
Valve
Equipment
Shutoff Valve
Flexible Gas Line
Do NOT Kink

WARNING: Test all gas piping and connections,





at once.
PRESSURE TESTING GAS SUPPLY PIPING SYSTEM

1. Disconnect replace and its individual equipment shutoff valve
from gas supply piping system. Pressures in excess of 1/2 psig
(3.5 kPa) will damage replace gas regulator.
2. Cap off open end of gas pipe where equipment shutoff valve
was connected.
3. Pressurize supply piping system by either opening propane/LP
supply tank valve for propane/LP gas replace or opening main
gas valve located on or near gas meter for natural gas replace,
or using compressed air.
4. Check all joints of gas supply piping system. Apply noncor-
rosive leak detection uid to all joints. Bubbles forming show
a leak. Correct all leaks at once.
5. Reconnect replace and equipment shutoff valve to gas supply.
Check reconnected ttings for leaks.

1. Close equipment shutoff valve (see Figure 33).
2. Pressurize supply piping system by either opening propane/LP
supply tank valve for propane/LP gas replace or opening main
gas valve located on or near gas meter for natural gas replace,
or using compressed air.
To Gas Supply
(Natural)
To External
Regulator
(Propane/LP)
Open
Figure 33 - Equipment Shutoff Valve
Closed
Equipment
Shutoff
Valve