Weber Weber Gas Grill User Manual


 
WWW.WEbEr.com
®
25
TYPICAL 20 LP PROPANE GAS SUPPLY INSTALLATION
The remote tank enclosure kit provided with your Weber Built-In grill shall be used for
installations using a 20 lb LP cylinder, mounted in an “island” structure.
The remote tank enclosure shall house the included hose and regulator assembly and
gas connections, the tank bracket and the fuel scale for connecting a remote mounted
LP cylinder to the Summit
®
Built-In gas grill. The hose and regulator is listed as a
required part of the CSA listed Summit
®
Built-In gas grill.
A properly installed tank enclosure meets the requirements for venting, tank retention
and separation of the LP cylinder from a heat source as outlined in the ANSI Standard
for Outdoor Cooking Gas Appliances, Z21.58/CSA 1.6 for LP enclosures.
You need to hire a licensed contractor or licensed plumber and they need to follow the
requirements described in the ANSI Standard for Outdoor Cooking Gas Appliances,
Z21.58/CSA 1.6 for LP enclosures.
The requirements described in the Standard for Outdoor Cooking Gas Appliances,
Z21.58/CSA 1.6. are as follows;
A remote enclosure for an LP gas cylinder shall be ventilated by openings at both
the upper and lower levels of the cylinder. This shall be accomplished by one of the
following:
A) One side of the remote LP cylinder enclosure shall be completely open; or
B) If the remote LP cylinder enclosure is designed to have four sides, a top and a
bottom, ventilation is required for the remote LP cylinder enclosure;
a) There should be at least two ventilation openings, (a hole or group of holes, for
the purpose of ventilation) in the sidewalls of the island structure. The openings
should be located within 5 inches (127 mm) of the top of the enclosure. The
ventilation openings should be equally sized and spaced at a minimum of 90
degrees, and be unobstructed. The openings shall have a total free open area
of not less than 20 square inches. (This relates to 1 square inch of ventilation
area, per pound of stored fuel capacity).
b) Ventilation openings (a hole or group of holes, for the purpose of ventilation)
should be provided at floor level. The ventilation openings should have a total
free area of not less than 10 square inches. (This relates to 1/2 square inch of
ventilation area, per pound of stored fuel capacity). There should be at least two
ventilation openings if the ventilation openings at floor level are in the sidewall.
The ventilation openings should be within 5 inches (127 mm) of the floor. The
ventilation openings should be of equal size and be spaced at a minimum of 90
degrees, and should be unobstructed.
c) The minimum size of the ventilation hole(s) should not be less than 1/4 inch.
d) The ventilation openings in the sidewalls should not allow venting into the
empty or “hollow” area of the “island”. If a gas leak should occur or the LP
cylinder should vent in the LP cylinder enclosure, the gas should not be allowed
to vent or migrate into the empty or “hollow” area of the “island”. Ventilation
openings in the sidewalls of the enclosure should only communicate with the
outside of the “island” structure, so that the gas can dissipate outside of the
“island” structure.
C) If the remote LP cylinder enclosure has four sides, a top and a bottom, and is
intended for installation in a built-in “island” enclosure;
a) At least one ventilation opening (a hole or group of holes, for the purpose of
ventilation) needs to be on one side of the enclosure that communicates with
the outside of the “island” structure. If a gas leak should occur or the LP cylinder
should vent in the LP cylinder enclosure, the gas should not be allowed to vent
or migrate into the empty or “hollow” area of the “island”. Ventilation openings
should only communicate with the outside of the “island” structure, so that
the gas can dissipate outside of the “island” structure. The ventilation opening
should be located within 5 inches (127 mm) of the top of the enclosure, and
should have a total free area of 20 square inches. (This relates to 1 square inch
of ventilation area, per pound of stored fuel).
b) At least one ventilation opening (a hole or group of holes, for the purpose of
ventilation) needs to be on one side of the enclosure that communicates with
the outside of the “island” structure, at the bottom. If a gas leak should occur
or the LP cylinder should vent in the LP cylinder enclosure, the gas should
not be allowed to vent or migrate into the empty or “hollow” area of the “island”.
Ventilation openings should only communicate with the outside of the “island”
structure, so that the gas can dissipate outside of the “island” structure. The
ventilation opening should be located within 5 inches (127 mm) of the bottom
of the enclosure, and should have a total free area of 10 square inches. (This
relates to 1/4 square inch of ventilation area, per pound of stored fuel).
c) The minimum size of the ventilation hole(s) should not be less than 1/4 inch
(6.35 mm).
D) The remote LP cylinder enclosure should be constructed with non-combustible
materials. The remote LP cylinder enclosure should isolate the LP cylinder from the
burner compartment, so that it provides shielding from radiation, be a flame barrier
and provide protection from foreign material such as hot drippings.
E) There should be a minimum of 2 inches (50.8 mm) between the ground and the
floor of the remote LP cylinder enclosure.
F) The LP cylinder valve should be readily accessible for hand operation. A door on the
remote LP cylinder enclosure to gain access to the LP cylinder valve is acceptable,
provided it is non-locking and can be opened without the use of tools.
m DANGER
Use of any hose and regulator assembly other than that
provided or recommended by Weber-Stephen Products LLC
could be dangerous, and may not provide adequate gas
supply to the Summit
®
Built-In gas grill, and could result in
a fire or an explosion causing serious bodily injury or death,
and damage to property.
m DANGER
Failure to build a remote LP cylinder enclosure for a
single 20 lb cylinder only, following the requirements for
ventilation, cylinder retention and separation of the LP
cylinder from a heat source, listed in the ANSI Standard
for Outdoor Cooking Gas Appliances, ANSI Z21.58 CSA
1.6, could be dangerous, and could result in a fire or an
explosion causing serious bodily injury or death and damage
to property.
If you do not follow the DANGER statements exactly, the Warranty on the Summit
®
Built-
In gas grill will be voided.
GaS SUPPLY