48049-136-05 Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Rev. 01, 07/2012 Section 3—Operation
© 1999–2012 Schneider Electric All Rights Reserved
25-EN
ENGLISH
Set communication module values:
1. Press and release scroll button to sequence
addresses (1 through 47). When the correct
address number is reached, enter the value
by pressing and holding scroll button until
the display stops flashing.
Baud rate screen will appear after address
has been entered.
Figure 36: Set Communication Module Values
2. Press and release scroll button to sequence
baud rates (4.8k, 9.6k or 19.2k). When the
desired baud rate appears, enter the value
by pressing and holding scroll button until
the display stops flashing.
Parity screen will appear after baud rate has
been entered.
3. Press and release scroll button to sequence
parities (E [even] or n [none]). When the
desired parity appears, enter the value by
pressing and holding scroll button until the
display stops flashing.
Languages screen will appear after parity
has been entered.
4. Press and release scroll button to scroll
through languages (French [Fr], US English
[En US], UK English [En], German [d],
Spanish [SP] or Italian [It]). When the
desired language appears, enter the value
by pressing and holding scroll button until
the display stops flashing.
Ammeter display will return to the default
screen after language is entered.
After the communication module values have
been set, ammeter will automatically return to
the current (i.e., default) menu.
After setting circuit breaker communication
module values, drawout circuit breakers must
have the cradle communication module, if
available, activated. For drawout circuit
breakers, refer to the cradle communication
module instructions to complete setup.