For propane/LP units, the installer must supply an
external regulator. The external regulator will re-
duce incoming gas pressure. You must reduce in-
coming gas pressure to between 11 and 14 inches
of water. If you do not reduce incoming gas pres-
sure, heater regulator damage could occur. Install
external regulator with the vent pointing down as
shown in Figure 19. Pointing the vent down pro-
tects it from freezing rain or sleet.
CAUTION: Use only new, black
iron or steel pipe. Internally-tinned
copper tubing may be used in
certain areas. Check your local
codes. Use pipe of 1/2" diameter
or greater to allow proper gas
volume to fireplace. If pipe is too
small, undue loss of volume will
occur.
Installation must include an equipment shutoff valve,
union, and plugged 1/8" NPT tap. Locate NPT tap
within reach for test gauge hook up. NPT tap must
be upstream from fireplace (see Figure 20).
IMPORTANT:
Install equipment shutoff valve in
an accessible location. The equipment shutoff
valve is for turning on or shutting off the gas to
the appliance.
Check your building codes for any special re-
quirements for locating equipment shutoff valve
to fireplaces.
Apply pipe joint sealant lightly to male NPT threads.
This will prevent excess sealant from going into
pipe. Excess sealant in pipe could result in clogged
fireplace valves. Never use sealant on flare threads.
WARNING: Use pipe joint
sealant that is resistant to liquid
petroleum (LP) gas.
We recommend that you install a sediment trap in
supply line as shown in Figure 20. Locate sediment
trap where it is within reach for cleaning. Install in
piping system between fuel supply and fireplace.
Locate sediment trap where trapped matter is not
likely to freeze. A sediment trap traps moisture and
contaminants. This keeps them from going into fire-
place gas controls. If sediment trap is not installed or
is installed wrong, fireplace may not run properly.
INSTALLATION
Continued
Figure 19 - External Regulator on
Propane/LP Supply Tank with Vent
Pointing Down
External
Regulator
Vent Pointing Down
Propane/LP
Supply Tank
Figure 20 - Gas Connection
* Purchase the optional CSA design-certified
equipment shutoff valve from your dealer. See Ac-
cessories, page 29.
** Minimum inlet pressure for purpose of input
adjustment.
Sediment Trap
3" Minimum
Cap Pipe Tee
Nipple Joint
CSA Design-Certified Equipment Shutoff
Valve With 1/8" NPT Tap*
Natural Gas
From Gas Meter
(5" W.C.** to
10.5" W.C.
Pressure)
Propane/LP
From External
Regulator
(11" W.C.** to
14" W.C.
Pressure)