Frigidaire Electric Patio Grill Electric Grill User Manual


 
13
General Information
Verify the type of gas supply to be used, either Natural Gas (NG) or Liquid Propane (L.P)., and make sure the
marking plate (located on the back of the unit) agrees with that of the supply.
Note: Never attach an unregulated gas line to the appliance.
For Natural Gas installations, an installer must supply a gas shutoff valve that is easily accessible to the grill.
All installer supplied parts must conform to local codes, or in the absence of local codes, with the National
Electrical Code, ANSI/NFPA 70-1990, and the National Fuel Gas Code, ANSI Z223.1-1998.
All pipe sealants must be an approved type and resistant to the actions of L.P. gases. Never use pipe sealant
on flare fittings. All gas connections should be made by a competent technician and in accordance with local
codes and ordinances. In the absence of local codes, the installation must comply with the National Fuel Gas
Code, ANSI Z223.1-1998. Gas conversions kits are available from the factory. When ordering gas conversion
kits have the model number, and the type of gas (natural or L.P.) from your grill.
This Grill and its individual shut off valve must be disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess of 1/2 PSIG (3.5 kPa.).
This Grill must be isolated from the gas supply piping system by closing its individual manual shut-off valve
during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG
(3.5 kPa.).
The installation of this Grill must conform with local codes, or in the absence of local codes , with National
Fuel Code, ANSI Z223.1a-1998.
Installation in Canada must be in accordance with the Standard Can1-b149.1 and or .2 (installation code for
gas burning appliances and equipment) and local codes.
Natural Gas Installation
The gas inlet supply pressure should be between 5” and 14” Water Column,(w.c.) A step down regulator is
required if the line pressure is in excess of 14” w.c. Inlet pressure must not exceed 14” water column (1/2
PSIG)
Check your local gas utility company or with local codes for instructions on installing gas supply lines. Be
sure to check on type and size of run, and how deep to bury the line. If the gas supply line is too small, the
grill will not operate correctly.
Any joint sealant used must be an approved type and be resistant to the actions of L.P. gases.
Attach the natural gas regulator (supplied with your grill) to the brass fitting coming out the bottom, backside
of the grill (be sure the arrow on the regulator is pointing up towards the grill). Attach your gas line to the
3/8” flare fitting coming out of the natural gas regulator at the back of the grill.
Place the installer supplied shut-off valve in an accessible location to enable the gas supply to be cut off to the
unit.
Gas Requirements