Enviro C-10100 Fire Pit User Manual


 
5) SOOTING
Make sure log placement is
in the correct location.
Correct to manufactures
specifications.
Correct if necessary.
Outside air supply may be
required on B-vented
models.
Make sure there is sufficient
air supply.
Check air shutter on the
venturi tube for proper
primary air adjustment.
SEE PAGE 16.
Increase primary air.
Open air shutter.
Make sure orifice matches
that on the rating plate.
Correct if necessary.
Make sure outlet (manifold)
pressure is correct.
Use a manometer to check
the gas pressure.
SEE PAGE 5 FIGURE 7.
Make sure the unit has been
derated for high altitude
applications.
(if required)
Correct if necessary.
Check to make sure that the
vent is drafting properly.
Correct if necessary.
Sherwood Industries Ltd. ENVIRO PAGE 15