Desa (V)K36EN SERIES Fire Pit User Manual


 
www.desatech.com
111924-01D10
Figure 15 - Horizontal Termination Conguration for Corner
Installation Using One 90° Elbow
Square
Termination
Wall
Firestop
Not to Exceed
(H) Limits
As Required for (V)
See Chart for Pipe
Section Required
45°
Elbow
90° Elbow
90° Elbow
Square
Termination
Wall
Firestop
45° Elbow
12" Minimum
Not to Exceed
(H) Limits
Square Termination
Vertical (V) Horizontal (H)
32
3
/
4
" min. 17" max.
Horizontal High
Wind Square
Termination
Wall Firestop
45° Elbow
CORNER AND ALTERNATE INSTALLATION
Recommended Applications:
Corner ground oor installation
Ground oor installation where pipe vents horizontally through
wall (over 12" horizontal pipe)
Basement installation where one foot clearance from ground to
termination is possible
VENTING INSTALLATION
INSTRUCTIONS
Continued
Adjustable
Pipe 12" Max.
Figure 14 - Horizontal Termination Conguration for Square
and Round Terminations
45° Elbow
Wall
Firestop
Horizontal
Round
Termination
Exterior Portion of
Wall Firestop (Round
Termination Only)

Figures 14 through 18 show different congurations and alterna-
tives for venting with horizontal termination. Each gure includes
a chart with critical minimum and maximum dimensions which
MUST be met. IMPORTANT: If using a venting conguration of
only horizontal venting with no vertical run, a 1/4" rise for every
12" of run toward the termination is required.
WARNING: Never run vent downward as this may
cause excessive temperatures which could cause a

venting system could result in serious injury, property
damage or loss of life.
GROUND FLOOR INSTALLATION
Recommended Applications:
Installation using cabinet surrounds
Through the wall using round or square termination (up to 12"
horizontal pipe)
NOT FOR CORNER INSTALLATION
Required
Vertical (V) Vertical Pipe Horizontal (H)
*43
1
/2" min. None 30" max.
54
1
/2" min. 1 ft. 48" max.
66
1
/2" min. 2 ft. 60" max.
78
1
/2" min. 3 ft. 84" max.
90
1
/2" min. 4 ft. 20' max.
*Ground Floor Corner Venting