Wells HDCB4830G Charcoal Grill User Manual


 
GAS APPLIANCE CODE COMPLIANCE
The installation of gas piping from the outlet side of the gas meter or
service regulator to the charbroiler must be performed by a technician
qualied and certied or licensed to install gas-red equipment.
A licensed and qualied technician must perform the initial startup and
adjustment of this appliance.
The installation of this gas-red appliance must conform to local codes,
or in the absence of such codes, with the current edition of
National Fuel Gas Code ANSI Z223.1.
For use in the State of Massachusetts, this appliance must be installed
in compliance with Massachusetts Fuel Gas and Plumbing Code
CMR 248.
The installation of this gas-red appliance must comply with applicable
portions of NFPA 96 for ventilation. The current edition of NFPA 96
(Standard for the Installation of Equipment for the Removal of Smoke
and Grease Laden Vapors from Commercial Cooking Equipment)
species ventilation requirements to ensure the removal of exhaust
gasses and products of combustion.
IT IS THE RESPONSIBILITY OF THE INSTALLER TO ENSURE
THAT THIS GAS GRIDDLE INSTALLATION CONFORMS TO ALL
APPLICABLE CODES AND ORDINANCES.
The venting of this appliance must not be obstructed, nor may such
venting interfere with the ow of combustion air required for proper
operation of the gas burners.
Additionally:
1. The gas supply line used to connect the appliance to the gas supply
system must be black iron pipe, or other material as approved by local
ordinance for gas piping.
2. Gas supply piping must be 3/4” inside diameter or greater.
3. Use pipe sealant made specically for gas piping on all pipe joints.
Apply sealant sparingly to the male threads only. Sealant must be
resistant to the action of LP gas.
4. Verify that all supply piping is clean and free of obstructions, dirt,
chips and pipe sealant compound prior to installation.
5. All pipe joints must be checked for leaks before lighting. Leak checks
should be performed with a soap and water solution.
NEVER CHECK FOR LEAKS WITH AN OPEN FLAME.
6. This appliance must be installed so that there is adequate and proper
clearance for operation and servicing.
INSTALLATION (continued)
5
DANGER:
FIRE AND
EXPLOSION
HAZARD
NEVER use an open ame to
check for gas leaks. Fire and
explosion may result.
WARNING:
RISK OF INJURY
Installation procedures must
be performed by a qualied
technician with full knowledge
of all applicable gas-red
appliance codes. Failure can
result in personal injury and
property damage.
IMPORTANT:
All pipe joints must be
checked for leaks before
lighting. Leak checks should
be performed with a soap and
water solution.
IMPORTANT:
Information on the
construction and installation
of ventilating hoods may be
obtained from the current
edition of NFPA 96 Standard
for the Installation of
Equipment for the Removal
of Smoke and Grease Laden
Vapors from Commercial
Cooking Equipment.
Copies of this standard are
available from the Nation Fire
Protection Assn.:
NFPA
1 Batterymarch Park
P.O. Box 9101
Quincy, MA 02269-9101
M163 2M-306981 Owners Manual for HDCB-Series Gas Char-Broilers
M163 2M-306981 Owners Manual for HDCB-Series Gas Char-Broilers