Summit 42369 Gas Grill User Manual


 
18
GAS LINE PIPING
Refer to the piping chart at the bottom of previous page.
The corrugated gas line from the manifold is 58 inches long. Do not
extend the gas line.
We have provided the means to make an SAE 45° fl are connection. Do
not use pipe sealant on this connection.
If the length of line required does not exceed 50 feet, use a 5/8” O.D.
tube. One size larger should be used for lengths greater than 50 feet.
Refer to piping chart.
Gas piping may be copper tubing, type K or L; polyethylene plastic tube,
with a minimum wall thickness of .062 inch; or standard weight (schedule
40) steel or wrought iron pipe.
Copper tubing must be tin-lined if the gas contains more than 0.3 grams
of hydrogen sulfi de per 100 cubic feet of gas.
Plastic tubing is suitable only for outdoor, underground use.
Gas piping in contact with earth, or any other material which may corrode
the piping, must be protected against corrosion in an approved manner.
Underground piping must have a minimum of 18” cover.
TEST CONNECTIONS
All connections and joints must be thoroughly tested for leaks in accordance
with local codes and all listed procedures in the latest edition of the National
Fuel Gas Code ANSI Z223.1/NFPA 54.
ƽ DANGER
Do not use an open fl ame to check for gas leaks. Be
sure there are no sparks or open fl ames in the area
while you check for gas leaks. This will result in a fi re
or explosion which can cause serious bodily injury or
death, and damage to property.
TYPICAL 20 LP PROPANE GAS SUPPLY INSTALLATION
We strongly recommend that you use the Summit
®
Built-In
Tank Cabinet (#21280) for installations using a 20 lb LP cylinder, mounted
remotely in an “island” structure.
The Summit
®
Built-In Tank Cabinet is a CSA listed accessory for installing a
remote mounted 20 lb LP cylinder, in an “island” structure. Summit
®
Built-In
Tank Cabinet has a hose and regulator assembly and gas connections, for
connecting a remote mounted LP cylinder to the Summit
®
Built-In gas grill. The
hose and regulator is listed as a required part of the CSA listed Summit
®
Built-
In gas grill.
The Summit
®
Built-In Tank Cabinet also meets the requirements for venting,
tank retention and separation of the LP cylinder from a heat source as outlined
in the ANSI Standard for Outdoor Cooking Gas Appliances, Z21.58/CSA 1.6
for LP enclosures.
The Summit
®
Built-In Tank Cabinet has its own installation guide.
If you do not use the Summit
®
Built-In Tank Cabinet, you need to hire
a licensed contractor or licensed plumber and they need to follow the
requirements described in the ANSI Standard for Outdoor Cooking Gas
Appliances, Z21.58/CSA 1.6 for LP enclosures.
The requirements described in the Standard for Outdoor Cooking Gas
Appliances, Z21.58/CSA 1.6. are as follows;
A remote enclosure for an LP gas cylinder shall be ventilated by openings at
both the upper and lower levels of the cylinder. This shall be accomplished by
one of the following:
a). One side of the remote LP cylinder enclosure shall be completely open;
or
b). If the remote LP cylinder enclosure is designed to have four sides, a top
and a bottom, ventilation is required for the remote LP cylinder enclosure;
1). There should be at least two ventilation openings, (a hole or group
of holes, for the purpose of ventilation) in the sidewalls of the island
structure. The openings should be located within 5 inches (127mm) of
the top of the enclosure. The ventilation openings should be equally
sized and spaced at a minimum of 90 degrees, and be unobstructed.
The openings shall have a total free open area of not less than 20
square inches. (This relates to 1 square inch of ventilation area, per
pound of stored fuel capacity).
2). Ventilation openings (a hole or group of holes, for the purpose of
ventilation) should be provided at fl oor level. The ventilation openings
should have a total free area of not less than 10 square inches. (This
relates to 1/2 square inch of ventilation area, per pound of stored
fuel capacity). There should be at least two ventilation openings
if the ventilation openings at fl oor level are in the sidewall. The
ventilation openings should be within 5 inches (127mm) of the fl oor.
The ventilation openings should be of equal size and be spaced at a
minimum of 90 degrees, and should be unobstructed.
3). The minimum size of the ventilation hole (s) should not be less than
1/4 inch.
4). The ventilation openings in the sidewalls should not allow venting into
the empty or “hollow” area of the “island”. If a gas leak should occur
or the LP cylinder should vent in the LP cylinder enclosure, the gas
should not be allowed to vent or migrate into the empty or “hollow”
area of the “island”. Ventilation openings in the sidewalls of the
enclosure should only communicate with the outside of the “island”
structure, so that the gas can dissipate outside of the “island” structure.
GAS SUPPLY