MONTANA INSTALLATION INSTRUCTIONS
9. Install the Termination Cap
If a roof flashing is to be used, install the roof flashing
appropriate to the roof pitch and install a round termination
cap following the instructions shipped with the cap.
For chase installations you can use a round termination cap
(TR11), a round telescoping termination cap (TR11T) or a
square termination cap (ST1175). A chase installation must
use a chase top. Chase tops are available from your
Heat-N-Glo distributor.
a. Install the chimney sections up through the chase
enclosure. When using a TR11 round termination cap,
the uppermost top section of pipe must extend 6 above
the top of the chase collar to allow installation of the storm
collar and termination cap. See Figure 14.
b. For installations utilizing a TR11T telescoping round
termination cap, the uppermost chimney section must
be below the top of the chase top, but not more than
14½ below the top of the chase top flashing collar. See
Figure 15.
c. For installations utilizing an ST1175 square termination
cap the last chimney section must not be more than 4½
below the chase top. See Figure 16.
d. Attach the chase top to the top of the chase.
e. Install the termination cap, following the
instructions provided with it.
Figure 15 - Installing a TR11T Round Telescoping
Termination Cap
Figure 14 - Installing a TR11 Round Termination Cap
Figure 16
Installing an ST1175 Square Termination Cap