Special offers from our partners!
Find Replacement BBQ Parts for 20,308 Models. Repair your BBQ today.
WWW.WEbEr.com
®
31
VENTILATION
m WARNING: Ventilation holes must be provided in the
structure at the top and bottom to provide ventilation in the
event of a gas leak.
Ventilation holes can be located in a low visibility area and should be protected by
screening material to prevent rodents and insects from entering the structure. Air holes
will also help dry moisture.
Note: These drawings are only a reference.
• Crossventilationmustbeincorporatedinthesupportingstructure.Werecommenda
minimum of 100 square inches (254 square cm) of venting per side.
• Ventsshouldbeontwosidesofthestructure.
• Thedrawingsareforreferenceonly.
• Locationoftheventsshouldbefromthecenter,outward.
• Locatetheventsatboththebottomofthestructureandatthetopofthestructure.
• Thebottomventsshouldbeasclosetogroundlevelaspossible.Makesurethevent
area is not blocked by interior supports of the structure.
• Werecommendventswithscreens.
• Accessdoorstothestructurearenotconsideredvents.
• Cleantheventsperiodically.
VENTILaTIoN
m DANGER
Failure to follow recommended minimum venting
instructions can cause gas to collect in the structure in the
event of a gas leak. This may result in a fire or an explosion
which can cause serious bodily injury or death, and damage
to property.
◆