Regency IG35 Gas Inbuilt Fireplace
16) Turn on gas supply and plug in power
cord.
Installer Notice:
These instructions must be left
with the appliance.
17) Adjusting the Outlet Pressure
All the adjustments must be carried out
in the following order:
Remove the modulator plastic cap (A) using
needle nose pliers.
Maximum pressure: Turn the unit ON to
its highest input rating. Screw in the nut (B)
to increase the outlet pressure and screw it
out to decrease it. Use a 10 mm wrench.
NOTE: The outlet pressure must be set to
maximum 2.61 kPa.
Minimum pressure: Remove one of the
cables connected to the electric modulator.
While holding the nut (B) with a wrench,
screw in the screw (C) to increase the
pressure and screw it out to decrease it.
Use a screwdriver 6 x 1 blade.
NOTE: The outlet pressure must be set to
minimum 0.75 kPa.
After carrying out all adjustments, block
the setting screws with paint, taking care
not to obstruct the breather ori ce of the
pressure.
Put back the modulator plastic cap.
WARNING: To ensure the correct opera-
tion of the modulator it is necessary that
the plastic cap (A) is returned to its original
location.
18) At the end of all setting and adjustment
operations, check electrical installation and
gas leaks.
19) Check operation of ame control.
20) Check for proper ame appearance and
glow on logs.
C
B
A
Cable
Electric
Modulator
INSTALLATION