KitchenAid KBSU367T Electric Grill User Manual


 
7
Built-in Outdoor Grill Enclosure Ventilation for LP Gas:
An enclosure for an LP gas fuel tank is to be ventilated by
openings at both the top and lower levels of the enclosure.
If converting to LP gas these vents are to be in the enclosure:
An enclosure for use with an LP gas fuel tank for built-in
installation is to have at least one ventilation opening on an
exposed exterior side located within 5" (12.7 cm) of the top is to
be a minimum of 20 in.
2
(129.0 cm
2
). One ventilation opening
within 1" (2.5 cm) of the bottom of the enclosure and the bottom
opening is to be a minimum of 10 in.
2
(64.5 cm
2
). All vent
openings are to be unobstructed. Every opening is to be a
minimum of ¹⁄₈" (0.32 cm) wide.
Electrical Requirements
If codes permit and a separate ground wire is used, it is
recommended that a qualified electrician determine that the
ground path is adequate.
Check with a qualified electrician if you are not sure whether the
grill is properly grounded.
A 120-volt, 60-Hz, AC-only, 15-amp, fused electrical supply is
required.
It is recommended that a separate circuit servicing only this grill
be provided.
The model/serial number rating plate is located on the right-hand
side of the grill. See the following illustration.
Recommended Ground Method
The outdoor grill, when installed, must be electrically grounded in
accordance with local codes or, in the absence of local codes,
with the National Electrical Code ANSI/NFPA 70, or Canadian
Electrical Code, CSA C22.1.
Copies of the standards listed above may be obtained from:
CSA International
8501 East Pleasant Valley Rd.
Cleveland, Ohio 44131-5575
National Fire Protection Association
One Batterymarch Park
Quincy, Massachusetts 02269
10 in.
2
(64.5 cm
2
) min.
ventilation both sides
5" (12.7 cm) max.
1" (2.5 cm) max.
20 in.
2
(129.0 cm
2
) min.
ventilation both sides
5" (12.7 cm) max.
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to follow these instructions can result in death,
fire, or electrical shock.
WARNING
A.Model/serial number plate
A. 3-prong ground plug
B. 3-prong polarized type outdoor outlet
C. Ground prong
A
A
B
C