Breckwell P23I Fire Pit User Manual


 
B. HORIZONTALLY THROUGH WALL
(refer to Figure 9)
NOTE: Follow L-Vent chimney
manufacturer’s instructions.
1. Position stove, adhering to
clearances shown in Figures 1 & 2.
2. Locate position of hole in wall;
directly behind stove exhaust vent
(refer to figure 5).
3. Always maintain 3” clearance from
combustible materials.
4. Install L-Vent wall thimble per L-Vent
manufacturer’s instructions.
5. Attach enough piping to penetrate
and extend at least 6” beyond
exterior walls. A minimum 8-foot
vertical pipe run is suggested where
possible to reduce the possibility of
smoke spillage in the event of a loss
of negative pressure.
6. Attach cap and seal outside wall
thimbles with non-hardening
waterproof mastic.
7. Termination should not be located so
that hot exhaust gases can ignite
trees, shrubs, or grasses or be a
hazard to children. Exhaust gases
can reach temperatures of 500ºF and
cause serious burns if touched.
Locate terminations: a) not less than 3 feet above any forced air inlet
located within 10 feet; b) not less than 4 feet below or horizontally from, or
one foot above, any door, window or gravity air inlet into any building; c) not
less than two feet from an adjacent building and not less than 7 feet above
grade when located adjacent to a public walkway. Mobile home installations
must use a spark arrester.
FIGURE 9
INSTALLATION
8